4.2.2. E1 MUX Specifications
The ANT BOSCH MUX will be used for E1 applications. Its specifications are shown below.
E1 - 30 B+D
Configured w/ 4...30 cards*
Mechanical Construction
10.51" x 19" x 12.2"
Weight
<26.4 lb
Power Requirements
Voltage -19 to -75V
Power Consumption 23W
Environmental Requirements
Temperature 5 to 40°C
*Must have card for each audio line
4.3. POWER DISTRIBUTION UNIT AND -48V POWER SUPPLY
Power Distribution Unit Specifications
The Power Distribution Unit (PDU) operates within the same environmental specifications as shown for the PI. The
operating environment must be free of corrosives or contaminants such as salt water or excessive dust. The following
environmental specifications should be met:
Temperature
Operating 0 to +40°C
Non-Operating -20 to 85°C
Humidity 20 to 90% noncondensing (except for removable diskette drive)
Storage Temperature -40 to +85°C
Operating Altitude < 15,000'
Shipping Altitude < 50,000'
-48V Power Supply Specifications
Specifications for the -48V power supply are shown below.
AC Input 100/120/220/240 VAC +10%, -13%, 47 to 63 Hz
Tolerance for 230 VAC operation is +15%, -10%
Derate output current is 10% for 50 Hz operation
DC Output -48 VDC, adjustment range is ±5% minimum
Line Regulation ±0.05% for a 10% change
Load Regulation ±0.05% for a 50% load change
Output Ripple 3mV +0.05% of output voltage, peak-to-peak maximum,
all "3-terminal regulator" outputs: 3mV +0.2% peak-to-peak
maximum
Short Circuit Protection Automatic current limit/foldback
Temperature Rating 0°C full rated, derated linearly to 40% at 70°C